Your Cart is empty!
Condition: New with Warranty Brand: Danfoss, Range: VLT HVAC FC 102
Danfoss VLT AutomationDrive FC 300 Series AC Frequency Inverter for 110kW (150HP) 400V 3 Ph motor to 212A at high overload (Heavy Duty) or 132kW (176HP) to 260A (Normal Duty) when Fan/Pump rated. Operates in VxF, Sensorless Flux Vector or Full Closed Loop Flux Vector control (when the optional encoder board is fitted).
Input Voltage - 380-500V Three Phase ±10% at 50-60Hz ±5%. Output Frequency: 0-590kHz Output Current at 400V: 260A (Normal Duty) or 212A (Heavy Duty) Input Current at 400V: 204A (Heavy Duty) or 241A (Normal Duty)
Protection Rating: IP20 Brake Chopper Not included RFI Filter:- Class A2/ (C3) Coated PCB's Option A: Not fitted Option B:MCB-101 General purp. I/O Option C: Not fitted Option D: Not fitted Graphicall Keypad Frame Size D3h Cubicle mount in clean environment. Rated at 45°C Ambient.
Net Weight: 62kg Gross Weight: 62.3Kg Dimensions: 909mm High x 250mm Wide x 375mm Deep Air Space: 225mm Below and above
Full part number is: 134F6784 Typecode is: FC-302N110T5E20H4XGCXXXSXXXXAXBKCXXXXDX
Download the Danfoss Manual and Design Guide from the links below .......
We've sent you a message containing a confirmation link. Click the link to complete the process.