Danfoss FC-102 Series AC Inverter for 30kW (40HP) 400V 3 Phase Fan or Centrifugal Pump in VxF control to 61A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction Motor.
Size B1: 242mm Wide x 200mm Deep x 480mm High. IP55.
Weight: 31kg.
Output Current (380-439V) 61A, (440-480V) 52A.
Overload: 110% x 60 seconds, 135% x 0.5 seconds.
Speed Control Range: 0-590Hz
Braking: None.
Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Relay Contact sets, DC Bus +/- Terminals, Terminals for RS485 Communications.
FC Protocol, N2 Metasys, FLN Apogee communication protocols built-in as standard.
Programmable from a PC via USB and free Danfoss MCT 10 software.
Input Current: 29A
Input Voltage: 380-480V Three Phase ±10% at 50-60Hz ±5%
EMC Compliance: IEC EN55011 First Environment Class C1 (Domestic and Industrial).
Wall mount in clean environment or cubicle mount.
Rated 45°C Ambient.
Ventilation space in front: [not specified], above and below: 100mm, at sides: 0mm.
Heat Loss at max output: 698W
Mounting via 4 x holes at rear on 210mm x 454mm centres.
Manufacturer part number is 131B3449.
Type code is: FC-102P18KT4E55H1XGXXXXSXXXXAXBXCXXXXDX.
Download the Danfoss FC102 Manual from the links below:-