Danfoss VLT FC-302 series AC Frequency Inverter for 7.5kW (10HP) 400V three phase motor in VxF control or Sensorless Flux control to 16A. Converts fixed frequency three phase 400V input to variable frequency three phase 400V to control the speed of a standard AC Induction motor or permanent magnet synchronous motor.
Frame Size A3: 268mm high x 130mm wide x 205mm deep. IP20.
Weight: 6.6kg
Overload: 160% for 60 seconds.
Speed Control Range: 0 - 590Hz in VxF Control, 0 - 300 Hz in Sensorless Flux Control.
Braking: to minimum 56 ohm external resistor (not included) 680W continuous. See linked products below for compatible resistor.
Graphical Keypad, 2 Analogue Inputs, 4 Digital Inputs, 1 Analogue Output, 2 Digital Input/Outputs, 2 Programmable Relay Outputs, Terminals for RS485 Communications.
1 x Safe Torque Off Input, Catagory 3 to SIL2, SILCL2, performance level "d".
Programmable from a PC via USB and free Danfoss MCT 10 software (see download link below).
Input Voltage: 380-500V Three Phase ±10% at 50-60Hz ±5%. Input Current 6.5A.
EMC Compliant to Class A1/B (C1/C2) Domestic Environment.
Cubicle mount.
Ventilation space above and below should be 100mm.
Heat Loss is 255W at full load.
Rated at 45°C Ambient. See Design guide for de-ratings for higher temperatures.
Part number: 131B0052
Type Code is: FC-302P7K5T5E20H1BGXXXXSXXXXAXBXCXXXXDX