ABB ACS380 series AC Inverter for 0.55kW 400V 3ph motor to 1.8A at high overload, or 0.75kW to 2.5A when fan/pump rated. Operates in standard V/F or Sensorless Vector Control and converts 400V 3ph fixed frequency input to 400V 3ph variable frequency output to control the speed of a standard AC Induction Motor, Permanent Magnet Synchronous motor or Synchronous Reluctance Motor.
ACS380-S: ACS380-N Base Unit and BMIO-01 I/O Expansion Module (additional loose item). BMIO-01 fits in the internal option slot ensurring no more internal options can be fitted
High Overload Rating: 0.55kW, 1.8A with 150% Overload for 60 seconds every 10 minutes
Light Duty Rating: 0.75kW, 2.5A with 110% Overload for 60 seconds every 10 minutes (Default)
Peak Rating: 3.2A for 2 seconds at Start-up.
Size R1: 70mm (W) x 205mm (H) x 176mm (D), 223mm (H) with Cable clamp. IP20
Weight: 1.4kg.
Speed Control Range: 0-599Hz
Dynamic Braking (DBr): 0.55kW (Max duty of 1 minute every 10 minutes). Min 99 Ohms, Max 628 Ohms external resistor (not supplied – see linked products below).
Fixed Operator Keypad with multi-line LCD Display
BMIO-01 included, supplied as a loose item; insert in option slot location (see photos)
With BMIO-01 fitted : 2 x Analogue Inputs, 4 x Digital Inputs, 2 x Digital Inputs/Outputs, 1 x Analogue Output, 1 x Relay Contact Set, terminals for Modbus RTU (EIA-485) communications.
Terminals for dual channel SIL3/PLe safe torque off (STO) included. (STO connections are fitted to the base unit not the BMIO-01)
No Internal option slot is available when BMIO-01 is fitted. When the ACS380-S is not fitted with the BMIO-01 module the ACS380 unit is equivalent to the ACS380-N version.
RJ45 Port available for Various External Keypads (see linked items below)
Can be programmed using Drivetune mobile App; Bluetooth Keypad ACS-AP-W is required for this; please see options below
Can be programmed using a PC with Drive Composer Software. Assistant Keypad ACS-AP-I, ACS-AP-S or ACS-AP-W or BCBL-01 Converter Cable is required for this; please see options below
Input Current: 3.8A. Reduces to 2.6A when fitted with an additional Input Choke.
Input Chokes reduce the input current but are also required if the short-circuit capacity of the network at the drive terminals is more than 5kA.
Input Voltage: Single Phase 200-240 Vac, +10%/-15%, 48 to 63 Hz
EMC compliance: EN 61800-3: 2004 + A1: 2012 Category C3 (Industrial)
Contamination Level: 3C2
Cubicle mount. For wall mounting in a clean environment NEMA kit is required.
Rated Ambient: 50°C
Ventilation space above: 75mm, below: 75mm, at sides: 0mm.
Heat Loss at max output: 44W.
Mounting via 35mm DIN rail or 4 x 5mm diameter slotted holes at rear
Manufacturer part number is ACS380-040S-02A6-4. Equivalent to ACS380-040S-02A6-4 +L538 (ACS380 unit with BMIO-01 factory fitted). Replacement product for ACS355