ABB ACS180 Series AC Inverter for 4kW 400V 3ph motor to 9.4A at high overload or 5.5kW to 12A when Fan/Pump rated. Operates in VxF or Sensorless Vector and converts fixed frequency Three Phase 400V input to variable frequency Three Phase 400V to control a standard AC induction, or permanent magnet synchronous motor.
Size R2: 120mm Wide x 143mm Deep x 202mm High. (230mm High with Earth Clamp) IP20.
Weight: 1.9kg.
Heavy Duty Rating: 9.4A with 150% overload for 60 seconds (Overload can be repeated once every 10 minutes)
Light Duty Rating: 12A with 110% overload for 60 seconds. (Overload can be repeated once every 10 minutes)
Peak Overload: 16.9A available at start up for 2 seconds
Speed Control Range: 0-590Hz.
Braking (DBr): Built-in braking switch. 75.7 Ohm resistor required for 100% Torque (continuous). 31.6Ohm resistor (minimum) for 10 seconds every 100 seconds (10% duty cycle). An external resistor is required for Dynamic Braking. Resistor is not supplied and should only be fitted if this feature is required see selection below.
Fixed Operator Keypad (*NO front mount Potentiometer*)
2 Analogue Inputs, 4 Digital Inputs (2 programmable for High Frequency), 1 Analogue Output, 1 Digital Output, 1 Relay Output (Change-over).
Safe Torque Off (STO) function to SIL3 (EN61800-5-2)
Serial Communications: Terminals for RS485 (Twin-Wire), Modbus RTU protocol.
RJ45 Port available for Various External Keypads (see linked items below; uses same internal port as Modbus RTU). See photo of ACS-AP Keypad and DPMP-02 Mounting Kit attached to an ACS180 to illustrate remote Keypad configuration.
Can be programmed using Drivetune mobile App; Bluetooth Keypad ACS-AP-W is required for this; please see options below
Can be programmed using a PC with Drive Composer Software. Assistant Keypad ACS-AP-I, ACS-AP-S or ACS-AP-W or BCBL-01 Converter Cable is required for this; please see options below
Input Current: 14.8A (11A when fitted with optional Input Line Reactor)
Input Voltage: 380-480V Three Phase (-15% +10%), 50/60Hz (47 to 63Hz)
EMC Compliance: IEC EN 61800-3 Category C3 (Industrial). EMC Filter Earth connection can be removed if required (screw). EMC Compliance achieved with motor cables up to 10m. External EMC Filters can be added for enhanced performance if required.
Cubicle mount.
Rated Ambient: 40°C (Fan/Pump Duty); 50°C (Heavy Duty)
Ventilation Space: Above: 75mm, below: 75mm, at sides: 0mm (at rated ambient)
Mount with 4 x M4 fixings (not supplied). For DIN mounting optional kit is required.
Ecodesign Classification: IE2
Heat Loss at max output: 157W
Standby Heat Loss: 12W
Efficiency at 90% Frequency and 100% Torque: 97.7%; Relative Losses 1.8%
Manufacturer Part Number: ACS180-04S-12A6-4
Replaces: ACS150