Eaton DG1 Series AC Inverter for 0.75kW (1HP) to 4.8A at High Overload or 1.1kW (1.5HP) to 6.6A when Fan/Pump rated. Operates in standard VxF or Sensorless Vector mode and converts fixed frequency three phase 230V Input to variable frequency three phase 230V to control the speed of a standard AC Induction motor.
High Overload Rating (Constant Torque):
Output Current: 4.8A; at 50 Degrees C; 4kHz Switching Frequency; Power Rating: 0.75kW / 1HP at 230V
OR
Fan/Pump Rating (Variable Torque):
Output Current: 6.6A; at 40 Degrees C; 4kHz Switching Frequency; Power Rating: 1.1kW / 1.5HP at 230V
Overload: 150% x 60 seconds (CT) or 110% x 60 seconds (VT) every 10 minutes.
Extended Overload: 200% x 2 seconds every 20 seconds.
Size 1: 327mm (H) x 153mm (W) x 201mm (D) IP21
Mounting via 4 x 7mm diameter holes at rear on 100mm x 312mm centres; Weight: 6.5kg
Speed Control Range: 0-400Hz
Dynamic Braking: Internal Brake Switch fitted for use with External Brake Resistor (not supplied)
Min Braking Resistance: 30Ohms; Brake Current: 30A continuous
Fitted with LCD Graphical Keypad.
2 x Analogue Inputs, 8 x Digital Inputs (1 can be configured for Thermistor Input), 2 x Analogue Outputs, 1 x Digital Output (Open Collector not Volt Free), 2 x Volt Free Change Over Contact & 1 x NO Contact (240VAC, 6A Max)
RJ45 Keypad Port; RJ45 Ethernet Port: RS485 Serial Port (Twisted Pair)
STO: Fitted as standard
Input Current: 4.4A (High Overload); 6.1A (Fan/Pump)
Input Voltage: 208-240V Three Phase +10% -15% at 50-60Hz ±10%
Input Choke: Not Required; DC Link Choke Fitted
EMC Compliance: IEC 61800-3; First Environment C2 (Commercial).
Cubicle Mount.
Ventilation space above and below: 100mm above; 50mm below, at sides: 20mm, in front: [not specified].
Heat Loss at max output: 60W (High Overload); 78W (Fan/Pump)
Manufacturer part number is DG1-324D8FB-C21C