Delta ME300 Basic Compact Series AC Inverter for 0.2kW (1/4HP) 115V/230V 3ph motor to 1,6A at high overload or 0.2kW (1/4HP) to 1,8A when Fan/Pump rated. Operates in VxF or Sensorless Vector and converts fixed frequency Single Phase 115V input to variable frequency Three Phase to 230V to control a standard AC induction, permanent magnet motor, IPM (Interior permanent magnet) and SPM (surface mounted permanent magnet).
Input Current: 1,6A at High Overload, 1,8A when Fan/Pump rated.
Input Voltage: Single phase AC 100–120 V (-15– +10%), 50/60 Hz.
Output: Variable to 230V Three phase.
EMC: None (Unfiltered)
Frame Size: A1 68mm Wide x 78mm Deep x 128mm High. IP20.
Mounting via 4 x M5 bolts (not supplied) at rear on 56mm x 118mm centres. (Optional DIN-Rail mounting available - see linked products below).
Weight: 0.4kg.
Overload:
150% for 60 seconds. High Overload. (Heavy Duty, HD), 200% of rated output current for 3 seconds.
120% for 60 seconds. Fan/Pump Rated. (Normal Duty, ND), 150% of rated output current for 3 seconds.
Speed Control Range: 0-599Hz. +/- 0.1%.
1 : 50 (V/f, SVC control for IM, heavy duty).
1 : 20 (SVC control for PM, heavy duty).
Switching (Carrier frequency): 2-15 kHz.
Braking (DBr): Built-in braking transistor for 125% Torque x 10 seconds every 100 seconds to 190 Ohm minimum external resistor (not supplied). See the Resistor options linked below, or use the 'Brake Resistor Calculator' link in the Information list below.
Product Features: Integrated Operator Keypad with integral potentiometer, (Option external keypad can be connected to the RS485 port (RJ45)) - see linked products below.
1 Analogue Input (0-10Vdc, 0-20mA & 4-20mA), 5 Programmable Digital Inputs (PNP/NPN), 1 Pulse Input (10kHz), 1 Analogue Output, 1 Digital Output,Modbus RS485 (RJ45)
1 Relay set of Changeover contacts (Resistive Load 3A/250VAC -5A/30VDC, Inductive Load 1.2A/250VAC -2A/30VDC)
Common DC Bus Terminals
Safe Torque Off (STO): Functional to SIL2 (EN61800), EN 60204-1 Category 0, EN 62061 SIL CL 2, SO 13849-1:2015 Category 3 PL d.
Environment and installation:
Pollution degree 2, Indoor use only, Cubicle mount only.
Rated at IP20
Humidity: 90%
Altitude: 0 ~ 1000m for normal operation
Heat Loss at High Overload: 18.6W total at max output
Cooling: Natural, no internal fan.
Ambient operating temperature to 50°C (40°C when units mounted side-by-side)
Ventilation space in front [not specified], above: 50mm, below: 50mm, at sides 30mm.
Certification: CE, UL, RoHS RCM, TUV, REACH, KC.
Manufacturer part number is VFD1A6ME11ANSAA