Danfoss VLT Micro Drive FC51 Series AC Frequency Inverter for 2.2kW (3HP) 400V 3 Phase Motor in VxF and Sensorless Vector Control (VVC) to 5.3A.
Supplied with Local Control Panel (Keypad) 132B0101 - with potentiometer
Output Current Rating: 5.3A
Overload: 150% x 60 seconds.
Size: M2 - 75mm Wide x 176mm Deep x 176mm High. IP20.
Weight: 1.6kg.
Speed Control Range: 0-200 Hz (VVC+), 0-400 Hz (VxF).
Braking (DBr): Internal Brake Switch Fitted (Does not have to be used; available if required)
Braking resistor (not supplied): 184.4 Ohm Nominal; 157 Ohm Minimum – see linked products below.
Keypad (HMI) is supplied as an additional item to be fixed to the front of the FC 51 unit.
2 x Analogue Inputs, 5 x Digital Inputs, 1 x Analogue Output, 1 x Relay Contact set.
Communications: RS485 (twin-wire); FC Protocol, Modbus RTU.
Programmable from a PC via Danfoss MCT 10 Software. (via RS485 port)
Input Current: 12.6A max
Input Voltage: 380-480V ±10% at 50-60Hz.
EMC Filters: To IEC/EN 61800-3 2nd Environment (Industrial); 1st Environment with restrictions – C2
Cubicle mount.
Ambient: Rated at 40°C
Ventilation space above and below: 100mm.
Ventilation space at sides: 0mm (drives can be mounted side by side)
Heat Loss at max output: 81.5W.
Mounting: Via 4 x 5mm diameter holes at rear on 59mm x 166.4mm centres
Full part number (without Keypad): 132F0022
Local Control Panel (Keypad) part number: 132B0101
Note: Supplied as 2 individual items, FC-51 drive unit and separate keypad for mounting of the front of the FC-51.
Type Code: FC-051P2K2T4E20H3
Download the Danfoss Micro Drive FC51 Manual from the link below:-